C1 PROTECTOR 8/16 CHANNEL
DISPLAY & ALARM CONTROLLER WITH MODBUS MASTER-SLAVE RS-485
PORTS
High resolution LCD with graphic display and channel-specific
indicator LEDs for quick problem identification
Alarm LEDs flash when new and become steady when acknowledged
Channel-specific display with short term and 24 hour trend
data
Sensor life reading available when using remote GASMAX gas
monitors
Three independent alarm levels per channel that include setpoint,
on/off delay, alarm above / below and voting options
Built-in calibration mode offers pushbutton zero / span calibration
for direct sensor interface applications
Analog input, direct bridge-type input or MODBUS master input
Standard outputs include four common relays (A1, A2, Fault,
Horn) plus MODBUS slave interface
Optional discrete channel-specific relays, 4-20mA outputs
and printer interface
Magnetic keypad available for nonintrusive operation in potentially
hazardous locations
CSA approved for Class I Div 2 areas without purge. CE mark
NEMA 4X, Explosion-Proof, panel and rack mount packaging options
available
Authorization Mode allows locking of critical configuration
variables
C1 Protector Controller provides simultaneous display and
alarm functions for up to 16 input channels. A graphic LCD
displays data as trends, bargraphs or engineering units. Three
adjustable alarm levels per channel with LED indicators are
provided. Four common relay outputs allow control of beacons,
horns and other alarm events. The horn relay may be set for
steady or pulsing operation.
Input options include an 8 channel analog input board (2x
for 16 inputs) and an 8 channel bridge-type input board (2x
for 16 inputs) with signal conditioning for direct interface
to GDS Corp catalytic bead, SmartIR or PID sensors. In addition,
a standard RS-485 MODBUS master port allows input data to
be retrieved from remote MODBUS slave devices such as GASMAX
II (wired) or GASMAX ECx or IIx (wireless) gas monitors. Any
channel can be programmed to accept data from either input
source. A standard RS-485 MODBUS slave port allows a remote
MODBUS master to read C1 setup and channel data in realtime.
Cross-connecting the master and slave interfaces allows two
controllers to act as a single unit.
C1 options such as channel-specific discrete alarm relays,
eight or sixteen 4-20mA outputs, MODBUS TCP and others can
be easily added for versatile system configurations that satisfy
the most challenging user applications.
The C1 is CSA certified for use in Class I, Division 2 potentially
hazardous areas and has C22.2 No. 152 approval for LEL combustible
receivers. Magnetic switch inputs allow operation of C1 controls
without opening the enclosure.
The C1 Protector Controller is available in panel mount,
rack mount, NEMA 4X composite or stainless steel and NEMA
7 explosion proof enclosures.
<Need More Info